PART 1-GENERAL
Submittal
Submit full size color sample(s) of each color specified or selected from manufacturer's color palette. Submit product literature, test reports, and product certifications.
Quality Assurance
Decorative (veneer) concrete masonry units shall be Optimum Series™
Oversize Masonry Units as manufactured by County Materials Corporation, Eau
Claire, WI (800-729-7701) and/or Premier Block Corporation, Eau Claire, WI
(888-395-5584). All units shall conform to ASTM C 90 Loadbearing Concrete
Masonry Units. Units shall be [specify style option] (Splitface, Ultra® Burnished,
Essence™ Fine Finish Split, Elite® Series or Sculpted) units as designated
on the drawings or in the specifications.
Field Constructed Mock-ups or
Sample Panels
Construct a separate (not part of the actual building) sample
wall panel not less than 4' by 4' with units in the pattern, color and shape
as indicated in drawings and specifications.
Cleaning agents and methods
shall be performed prior to approval of the sample panel. Walls erected without
a sample panel will be considered approved "as is".
Delivery, Storage and
Handling
Optimum Series™ Oversize Masonry Units shall be delivered to
the job site on pallets and stacked only one pallet high on level ground. Delivered
pallets shall be protected from inclement weather with a waterproof covering.
Units shall be handled carefully to avoid breakage and damage.
Design Practices and Installation
Careful consideration should be given to the placement of control
joints and the use of horizontal joint reinforcement, brick wall ties, weep
holes and water-resistant sealants. It is expected that Optimum Series™ Oversize
Masonry Units will be laid using the best concrete masonry construction practices.
For maximum construction efficiency and economy, concrete masonry walls should
be designed and constructed with modular coordination in mind. Standard dimensions
for Optimum Series™ Oversize Masonry Units are equal to the nominal dimensions,
less the thickness of one mortar joint (3/8"). Optimum Series™ Oversize
Masonry Units should not be wetted prior to placement.
Control Joints
Control joints are one method used to relieve horizontal tensile
stresses due to shrinkage of concrete masonry units, mortar, and when used,
grout. They are essentially vertical separations built into the wall at locations
where stress concentrations may occur. These joints reduce restraint and
permit longitudinal movement. Concrete masonry requires vertical control joints
to accommodate panel contraction.
Control Joint Placement
Control joints should be located where volume changes in the
masonry due to drying shrinkage, carbonation, or temperature changes are likely
to create tension in the masonry that will exceed it's capacity. The following
are suggested methods to provide guidance in locating control joints.
1. At changes in wall height,
2. At changes in wall thickness, such as at pipe and duct chases
and pilasters,
3. At (above) movement joints in foundations and floors,
4. At (below) movement joints in roofs and floors that bear on
the wall,
5. Near one or both sides of door and window openings, (generally,
a control joint is placed at one side of an opening less than 6 ft wide and
at both jambs of openings over 6 ft wide). Control joints can be away from
the opening if adequate tensile reinforcement is placed above, below and beside
wall openings. Adjacent to corners of walls or intersections within a distance
equal to half the control joint spacing requirement for that wall.
For more detailed control joint spacing, see NCMA Tek Note
10-2B.
|
 |
Empirical Crack Control
For walls without openings or other points of stress concentration,
control joints are used to effectively divide a wall into a series of isolated
panels. Table 1 lists recommended maximum spacing of these control joints based
on empirical criteria. For walls containing masonry parapets, consider the
parapet as part of the masonry wall below if it is connected by masonry materials
such as a bond beam unit when determining the length to height ratio.
The control joint spacings of Table 1 have been developed based
on the use of horizontal reinforcement to keep unplanned cracks closed as
indicated in footnote.
Horizontal Joint Reinforcement
Continuous, 4"
joint reinforcement is required for every course in all veneer applications
and in the exterior wythe of composite wall construction. Nonstructural,
horizontal, joint reinforcement, should not be continuous through a control
joint, since this will restrict the horizontal movement. However, structural
reinforcement, such as bond beam reinforcement at floor and roof diaphragms
that resists diaphragm cord tension, must be continuous through the control
joint, but provisions should be allowed for longitudinal movement.
Weep Holes
To properly drain water collected on any flashing or horizontal
surface, weep holes must be provided immediately above the flashing or horizontal
surface at all locations, following standard industry practices. Weep holes
should be at least 1/4 inch in diameter, and should be spaced no further apart
than 32 inch. o.c. horizontally. When using wick type material in the weep
hole, the spacing should be reduced to a maximum of 16 inch o.c.
Veneer Anchors
County Materials Corporation and Premier Block Corporation recommend
using an anchor that allows for vertical and horizontal movement. Examples
are DW-10 manufactured by Hohman Barnard or Type III veneer anchor w/triangular
tie manufactured by Wire Bond.
Flashing
The primary role of flashing is to intercept the flow of moisture
through masonry and direct it to the exterior of the structure. Flashing is
recommended for all locations where moisture may potentially penetrate into
a wall and where the free drainage of water is blocked. Some of these critical
locations include the top of walls and parapets, at all horizontal obstructions
such as over openings, beneath sills, above shelf angles, and at the base of
walls. Flashing may also be utilized in walls at ground level to serve as a
moisture retarder to reduce the amount of water wicked up into the masonry
above grade. Weep holes and vents also reduce the moisture content of masonry
walls.
Project/Site Conditions
During construction of exposed concrete masonry, minimize mortar
and grout smears on the face of the units. Mortar droppings that adhere to
the exposed face of the units can be removed with a trowel or chisel after
being allowed to harden. Any remaining mortar can then be removed with a stiff
fiber brush. The base of the wall should be protected from mud splashing and
mortar droppings by spreading plastic sheets four feet on the ground and three
feet up the wall. Covering the tops of unfinished walls at the end of the workday
prevents rain and outside elements from entering the wall and thus reduces
the chance of efflorescence forming on the wall. Covers should be draped at
least two feet down each side of the wall and a method provided to hold them
in place.
|
 |
Mortar and Mortar Joints
Use regular gray or a complementary color to match the Optimum
Series™ Oversize Masonry Units. Concave or V-shaped tooling of joints, when
the mortar is thumbprint hard, improves moisture resistance by compacting the
mortar against the masonry unit to seal the joint. Raked, flush, struck, beaded,
or extruded joints are not recommended as they do not compact the mortar and/or
create ledges that intercept water running down the face of the wall. Head
and bed joints should be the full thickness of the face shells for optimum
water tightness.
Cleaning
Optimum Series™
Oversize Masonry Units can be cleaned using traditional
masonry cleaning methods, such as mild masonry detergents/cleaners and power-washing
systems properly applied. Strong acids, acid washes or chemicals with a strong
acid reaction should not be used, since they may reduce the water repelling
properties of treated masonry and etch the surface, distorting the color.
Keep the masonry wall clean as the construction progresses and use a brush
and water after the mortar has hardened.
Water Repellents
Optimum Series™ Oversize Masonry Units are manufactured with
integral water repellents. This is to provide resistance to wind-driven rain,
reduce the potential for efflorescence and staining from environmental pollutants,
and enhance the color and texture of a wall. The same water repellent admixture
should be used in the mortar, as was used in the block, to ensure compatibility
and bond.
Extreme Weather Construction
Temperatures between 40 and 90°F (4.4 and 32.2°C) are
considered
"normal" temperatures for masonry construction and therefore do not
require special procedures or protection protocols. When ambient temperatures
fall below 40°
F (4.4°C), the Specification for Masonry Structures requires consideration
of special construction procedures. Similarly when the minimum daily temperature
for grouted masonry or the mean temperature for ungrouted masonry falls below
40°F (4.4°C) during the first 48 or 24 hours after construction respectively,
special protection considerations are required.
Rain and Masonry Construction
The presence of rain, or the likelihood of rain, should receive
special consideration during masonry construction. Unless protected, masonry
construction should not continue during heavy rains, as partially set or plastic
mortar is susceptible to washout, which could result in reduced strength or
staining of the wall. However, after approximately 8 to 24 hours of curing
(depending upon environmental conditions), mortar washout is no longer of concern.
When rain is likely, all construction materials should be covered. Newly constructed
masonry should be protected from rain by draping a weather-resistant covering
over the assemblage. The cover should be secured in place and extend over all
mortar that is susceptible to washout.
(References: National Concrete Masonry Association TEKs)
County Materials Corporation Corporate Office
205 North Street,
P.O. Box 100
Marathon, WI 54448
800-289-2569
Premier Block Corporation
Corporate Office
1111 Menomonie Street
P.O. Box 910
Eau Claire, WI 54702
888-395-5584
|